Technical data EL1018 Connection technology 1-wire Specification EN 61131-2, type 1/3 Number of inputs 8 Nominal voltage 24 V DC (-15%/+20%) “0” signal voltage -3…+5 V (EN 61131-2, type 3) “1” signal voltage 11…30 V (EN 61131-2, type 3) Input current typ. 3 mA (EN 61131-2, type 3) Input filter typ. 10 µs Distributed clocks – Current consumption power contacts typ. 2 mA + load Current consumption E-bus typ. 90 mA Electrical isolation 500 V (E-bus/field potential) Configuration no address or configuration setting Special features standard input terminal for fast signals (filter 10 μs) Weight approx. 55 g Operating temperature -25…+60°C Storage temperature -40…+85°C Relative humidity 95%, no condensation Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27 EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4 Protect. rating/installation pos. IP20/see documentation Pluggable wiring level for all ESxxxx terminals Approvals/markings CE, CCC, UL, ATEX, IECEx, DNV Ex marking ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc