Schneider 3DM2-WRDUWZ Protection Relay Malaysia
Specifications
Main
|
Range of product |
EOCR |
|
Device short name |
EOCR-3DM2 |
|
Product or component type |
Protection relay |
|
Protection type |
Overload, In > OC setting
Underload, In < UC setting
Locked rotor for starting, In > 2...8 times OC setting
Locked rotor for running, In > 1.5...5 times OC setting
Sensitivity to phase loss
Phase unbalance, 10...50 %
Sensitivity to phase reverse |
|
Product specific application |
Motor protection |
|
Network type |
AC |
|
Network frequency |
50...60 Hz |
|
protection ajustment range |
0.5…80 A |
|
Tripping threshold |
0.5...80 A (definite)
0.5...32 A (inverse and thermal) |
Complementary
|
[Us] rated supply voltage |
100...240 V AC/DC |
|
Mounting support |
35 mm DIN rail
Panel |
|
Contacts type and composition |
1 NC + 1 NO (OL)
1 NO (AL/UL/TO) |
|
Short-circuit and overload protection |
By 4 A gG fuse |
|
[Ue] rated operational voltage |
600 V AC 50...60 Hz for power circuit conforming to UL
690 V AC 50...60 Hz for power circuit conforming to CSA
690 V AC 50...60 Hz for power circuit conforming to IEC 60947-4-1 |
|
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-4-1 |
|
Reset |
Manual reset
Automatic reset 0.5…1200 s
Electrical 0…1 s by interruption of power supply |
|
Time delay type |
D-Time: 0...200 s
O-Time: 0.2...30 s (definite)
O-Time: 1...30 class (inverse and thermal)
U-Time: 0.5...30 s |
|
Display type |
Bar graph
7 segments LED |
|
power consumption per relay |
3 W |
|
Connections - terminals |
Control circuit: cable 2 x 1…1.5 mm²flexible with cable end - M3
Control circuit: cable 2 x 1…1.5 mm²flexible without cable end - M3
Control circuit: cable 1 x 1…2.5 mm²flexible with cable end - M3
Control circuit: cable 1 x 1…2.5 mm²flexible without cable end - M3 |
|
Tightening torque |
Control circuit: 0.8...1.2 N.m on cable, 4.7 mm |
|
Height |
74.5 mm |
|
Width |
70 mm |
|
Depth |
83.8 mm |
|
Product weight |
0.315 kg |