Schneider V0C Switch Disconnector Malaysia
Specifications
Main
|
Range |
TeSys |
|
Product Name |
TeSys VARIO |
|
Device Short Name |
V |
|
Product Type |
Switch body |
Complementary
|
Mounting Support |
Symmetrical rail
Plate |
|
Performance Level |
High performance |
|
Number of Poles |
3P |
|
Contact Type and Composition |
3 NO |
|
Network type |
AC
DC |
|
Network frequency |
50/60 Hz |
|
[Ue] IEC Rated Operational Voltage |
690 V AC 50/60 Hz |
|
IEC Rated Operational Power in W |
11 kW at 500 V (AC-23A)
11 kW at 690 V (AC-3)
15 kW at 690 V (AC-23A)
4 kW at 230...240 V (AC-3)
5.5 kW at 400...415 V (AC-3)
7.5 kW at 500 V (AC-3)
5.5 kW at 230...240 V (AC-23A)
7.5 kW at 400...415 V (AC-23A) |
|
[Ie] Rated Operational Current |
14.5 A AC-23 Ue: 400 V |
|
[Ith] Conventional Free Air Thermal Current |
25 A |
|
[Ithe] Conventional Enclosed Thermal Current |
20 A |
|
Making capacity ( I Rms) |
250 A at 400 V AC-21A
250 A at 400 V AC-22A
250 A at 400 V AC-23A |
|
Breaking Capacity |
200 A at 400 V (AC-21A)
200 A at 400 V (AC-22A)
200 A at 400 V (AC-23A) |
|
Rated Conditional Short Circuit Current |
10 kA at 400 V - associated fuse 25 A aM
10 kA at 400 V - associated fuse 25 A gG |
|
[Icm] Rated Short Circuit Making Capacity |
1 kA at 400 V at Ipeak |
|
Intermittent duty class |
30 |
|
Suitability for isolation |
Yes |
|
[Uimp] rated impulse withstand voltage |
8 kV |
|
[Icw] rated short-time withstand Rms current |
300 A at 400 V duration: 1 s |
|
Mechanical Durability |
100000 cycles |
|
Electrical Durability |
100000 cycles AC-21
30000 cycles DC-1...5 |
|
IEC Terminal Connection |
Power circuit: screw clamp terminals10 mm² - solid
Power circuit: screw clamp terminals6 mm² - flexible - with cable end |
|
Tightening Torque |
Power circuit: 2.1 N.m - on screw clamp terminals |
|
Height |
74 mm |
|
Width |
55 mm |
|
Depth |
60 mm |
|
Product Weight |
0.2 kg |