Technical data EL3102
Number of inputs 2 (differential)
Power supply via the E-bus
Signal voltage -10…+10 V
Oversampling factor
Input signal bandwidth
Distributed clocks yes
Distributed clock precision << 1 µs
Internal resistance > 200 kΩ
Input filter limit frequency 5 kHz
Common-mode voltage UCM max. 35 V (relative to the internal GND)
Conversion time ~ 60 µs (fast mode ~ 40 µs)
Resolution 16 bit (incl. sign)
Measurement error/ uncertainty < ±0.3% (relative to full scale value)
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bus typ. 170 mA
Bit width in the process image inputs: 8 byte
Special features standard and compact process image, switchable measuring data representation, activatable FIR/IIR filters, limit value monitoring
Operating/storage temperature -25…+60°C/-40…+85°C
Weight approx. 60 g
Relative humidity 95%, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx
Pluggable wiring for all ESxxxx terminals
Ex marking ATEX:
II 3 G Ex ec IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc